CHARNWOOD
COUNTRY 14B
Roomheater with Boiler
Operating
and
Installation Instructions
C H A R N W O O D B i s h o p s W a y , N e w p o r t , I s l e o f W i g h t P O 3 0 5 W S , U n i t e d K i n g d o m
T : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 9 9 F : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d @ a j w e l l s . c o . u k w w w . c h a r n w o o d . c o m
or fire lighters, and kindling on the
grate and cover with approximately 2
inches of fuel. Turn the control knob
to maximum, and open the airwash
control fully (see Fig. 1). Light the
paper or fire lighters. Close the doors
until the fuel is well ignited then load
with fuel and adjust the air controls to
the required setting.
firebox in two stages waiting between
each stage for the flames to appear
above the fire.
REFUELLING
Keep the firebox well filled but do not
overfill to prevent fuel from spilling
over the top of the front fire bars.
After a period of slumbering always
turn the air control up to maximum
and wait until flames appear above the
fuel bed before opening the doors.
Care should be taken especially when
burning wood that fuel does not
project over the front fire bars or
damage to the glass may be caused
when the doors are closed, it can also
cause the glass to black up.
Burning coal will produce more soot
deposits than other fuels, especially if
the fire is run at low levels for long
periods. It is therefore vital to clean
the throat plate regularly, weekly
cleaning is recommended.
On initial lighting, the stove may
smoke and give off an odour as the
silicon paint with which the firebox is
painted reacts to the heat. This is
normal and will cease after a short
time, but meanwhile the room should
be kept well ventilated.
Never fully close the Airwash control
when burning coal.
When relighting the stove, riddle (if
burning solid fuel), remove any
clinker from the firebed and then
empty the ashpan.
SPECIAL POINTS
WHEN BURNING
WOOD AND PEAT
CONTROLLING THE
FIRE
The rate of burning and hence the
output is controlled by the control
knob on the side of the fire and the
airwash control (see Fig.1).
The grate should be kept in the wood
burning position and should not be
riddled until the ash becomes so deep
that it begins to block the passage of
air into the firebox at the side of the
grate. When this is the case do not
remove all of the ash using the
Solid Fuel
Riddle
riddling mechanism but keep a layer
about half an inch thick as this enables
the wood to burn more effectively.
When burning wood or peat use the
airwash control in the same way as
described (see "CONTROLLING
THE FIRE" )
The control knob is linked to a
thermostat which senses the boiler
temperature. The number at the front
of the knob is the number at which it
is set.
Wood
The airwash control should be kept at
least slightly open most of the time to
keep the glass clean. It may be fully
opened when rapid heating is required
or to help clean any deposits from the
glass. It will not be possible to keep
the glass clean if this control is fully
closed, particularly immediately after
refuelling.
OVERNIGHT
BURNING
For overnight burning the fire doors
must be closed.
Fig 2. Grate Operation
ASH CLEARANCE
The ashpans should be emptied
When burning solid fuel the ashpans
should be emptied and the fire riddled.
If the fire is very low then it may be
necessary to add a little fuel and turn
the thermostat control up to maximum
for a brief period until the fire is
burning brightly before filling with
fuel. When the new fuel has ignited,
the thermostat control should be
turned down to the required setting
and the airwash control moved to a
low setting. If the central heating
pump is off overnight then the
regularly before it becomes too full.
Never allow the ash to accumulate in
the ashpans so that it comes in contact
with the underside of the grate as this
will seriously damage the grate bars.
The ashpans are handled using the tool
provided. Care should be taken to
ensure that ash is cool before
RIDDLING
When burning solid fuels riddling
twice a day is usually sufficient. When
burning wood or peat, ash should be
allowed to build up and generally
weekly riddling will be sufficient. The
fire should be riddled with the doors
shut (see Fig 2.) Place the tool onto
the riddling lever and rotate between
the 1 o'clock and 3 o'clock positions
several times. Too much riddling can
result in emptying unburnt fuel into
the ashpan and should therefore be
avoided. If any clinker forms it should
be removed from the firebed. After
riddling, the grate should be put back
into the solid fuel or wood position as
required (the tool should be in the 1
o'clock position for solid fuel or in the
5 o'clock position for wood).
emptying it into plastic liners or bins.
To make ash removal easier there is a
special Charnwood ash carrier
available. This may be purchased from
your supplier or, in case of difficulty,
from ourselves.
thermostat may be left at the same
setting for both day and night
operation. If the central heating pump
is on overnight then set the thermostat
control to give the required level of
heating. Some experimentation will be
necessary to find the settings most
suitable for the particular fuel used
and the draw on the chimney.
SPECIAL POINTS
WHEN BURNING
COAL
When loading the stove take care not
to smother the fire, instead fill the
To revive the fire, empty the ashpans,
Page 2
Country 14B 09/03
riddle, and open the air controls to
maximum. When the fire is burning
well load on more fuel as necessary
and move the air controls to the
desired setting.
retaining lugs.
that a suitable fuel is being used, d)
that there is an adequate air supply
into the room,
e) that an extractor fan is not fitted in
the same room as the stove.
f) there is sufficient draw in the
chimney, (once the chimney is warm a
draught reading of at least 0.10 inches
water gauge should be obtained).
CHIMNEY SWEEPING
The chimney should be swept at least
twice a year. Where a top outlet is
used it will generally be possible to
sweep the chimney through the
appliance.
When burning wood use large logs
rather than small ones. Proceed as
above, but do not riddle the fire either
when shutting down or reviving.
First remove the side fire plates, front
firebars and the throat plate. Then
sweep the chimney ensuring that soot
is removed from all horizontal
surfaces after sweeping.
Door Glass Blacks Up
CLEANINGAND
MAINTENANCE
The stove is finished with a high
temperature paint which will
Keeping the glass clean requires a
certain amount of experimentation due
to the differences in the draw of
different chimneys. The following
points should be noted and with a little
care should enable the glass to be kept
clean in most situations:
In situations where it is not possible to
sweep through the appliance the
installer will have provided alternative
means, such as a soot door. After
sweeping the chimney the appliance
flue outlet and the flue pipe
withstand the temperatures
encountered in normal use. This may
be cleaned with a damp lint-free cloth
when the stove is cold. Should re-
painting become necessary, high
temperature paints are available from
your supplier or from stove shops.
a) The airwash relies on a supply of
heated air to keep the glass clean,
therefore, when lighting the stove
allow the firebed to become well
established before closing the air
controls. This may also be necessary
when re-fuelling the stove.
connecting the stove to the chimney
must be cleaned with a flue brush.
The glass in the doors is a zero
expansion ceramic glass, capable of
withstanding the heat of the fire.
After clearing any soot from within
the stove, replace the throat plate (see
Fig. 3), the front firebars, and side
fireplates.
Before cleaning the glass open the
doors and allow them to cool. Clean
the glass using a damp cloth and then
wiping over with a dry cloth. Any
stubborn deposits on the glass may be
removed with a proprietary stove glass
cleaner or ceramic hob cleaner. Some
deposits on the glass may be burnt off
simply by running the fire at a fast rate
for a few minutes. Do not use abrasive
cleaners or pads as theses can scratch
the surface which will weaken the
glass and cause premature failure.
b) When re-fuelling keep the fuel as
far back from the front firebars as
possible, do not try to fit too much
fuel into the firebox.
Different types of sweep's brushes are
available to suit different flueways.
For standard brick chimneys a wire
centre sweep's brush fitted with a
guide wheel is recommended. For
prefabricated insulated chimneys the
manufacturers instructions with regard
to sweeping should be consulted.
c) Never completely close the airwash
control - as a guide it should be at
least a quarter open.
d) Wet wood or logs overhanging the
front firebars will cause the glass to
blacken.
It is always more difficult to keep the
glass clean when running the stove
very slowly for long periods.
THROAT PLATE AND
FLUEWAY CLEANING
It is important that the throat plate and
all the stove flueways are kept clean.
When burning smokeless fuels they
should be cleaned monthly. When
burning other fuels they should be
cleaned at least once a week, and more
frequently if necessary. It is not
If blackening of the glass still occurs
check that all flue connections and the
blanking plate are well sealed. It is
also important that the chimney draw
is sufficient, (when the chimney is
warm a draught reading of at least
2.54 mm, or 0.10 inches, water gauge
should be obtained), and that it is not
affected by down-draught.
Tool
Pull Forward
Swing Down
necessary to let the fire out completely
to carry out these operations.
When burning coal some blackening
of the glass may occur below the level
of the front firebars. This will not
obscure the view of the fire or affect
its performance.
The throat plate is lowered using the
door opening tool. Slide the tool into
the bracket from the side, pull the
throat plate forward, and then lower it
as shown in Fig. 3. Any sooty deposits
should then be swept from the plate
and into the fire.
Fig.3 Throat Plate Location
Fume Emission.
TROUBLE SHOOTING
Fire Will Not Burn.
Check that:
a) the air inlet is not obstructed in any
way,
Warning Note: Properly installed
and operated this appliance will not
emit fumes. Occasional fume from
de-ashing and re-fuelling may occur.
Persistent fume emission is
potentially dangerous and must not
be tolerated. If fume emission does
persist, then the following
While the throat plate is lowered clean
any sooty deposits from the boiler
faces and the airwash tubes.
Return the throat plate to its correct
position - raise the front of the plate,
push it back and then lower it onto the
b) chimneys and flueways are clear, c)
Page 3
Country 14B 09/03
immediate actions should be taken:
f) Door seals and airwash slide are
intact.
b) the throat plate is fitted correctly
(see Fig. 3.) and that it is not distorted.
c) the door seals are in good condition.
d) If the hot water goes cold when the
pump is turned on, or if some radiators
are hotter than others, then the system
may need balancing, the pump may be
pumping the water too quickly around
the system, or the radiators may need
bleeding. Please ask your installer to
check these points.
a) Open doors and windows to
ventilate the room.
b) Let the fire out and safely dispose
of the fuel from the appliance.
c) Check for flue or chimney
blockage, and clean if required.
d) Do not attempt to re-light the fire
until cause of fume has been
identified, if necessary seek
professional advice.
Over-Firing
If the fire is over-fired it will cause
premature failure of the internal fire
parts. Overfiring is occurring when
any parts of the fire begin to glow red.
To prevent over-firing ensure that:
a) the door seals are kept in good
condition, and that the doors are
sealing correctly,
b) the thermostat on the fire is
working correctly,
c) a suitable fuel is being used,
d) the fire is not fitted onto a heating
system which is too large.
The most common cause of fume
emission is flueway or chimney
blockage. For your own safety these
must be kept clean.
Chimney Fires.
If the chimney is thoroughly and
regularly swept, chimney fires should
not occur. However, if a chimney fire
does occur turn the controls to the
minimum setting, and tightly close the
doors of the appliance. This should
cause the chimney fire to go out in
which case the controls should be kept
at the minimum setting until the stove
has gone out. The chimney and
flueways should then be cleaned. If
the chimney fire does not go out when
the above action is taken then the fire
brigade should be called immediately.
Fire blazing out of control
Check that :
Freezing
Do not light the fire if there is any
possibility that any parts of the system
may be frozen.
a) The doors are tightly closed.
b) The aircontrols are set at the
minimum setting.
c) the thermostat flap is closed (at the
bottom of the left hand side of the
appliance, see Fig. 1.) and that it is not
prevented from closing completely by
a piece of ash,
Lack of Heat To
Radiators / Hot Water
After a chimney fire the chimney
should be carefully examined for any
damage. Expert advice should be
sought if necessary.
d) The airwash control is closed.
e) A suitable fuel is being used.
Check that:
a) the fire is burning properly - if not
then carry out the checks under "Fire
Will Not Burn".
Page 4
Country 14B 09/03
INSTALLATION INSTRUCTIONS FOR THE
CHARNWOOD COUNTRY 14B
complete chimney.
HEALTH AND SAFETY
CHIMNEY
If it is found that there is excessive
draw in the chimney then a draught
stabilizer should be fitted.
PRECAUTIONS
In order for the appliance to perform
satisfactorily the chimney height must
not be less than 4 metres measured
vertically from the outlet of the stove
to the top of the chimney. The internal
dimensions of the chimney should
preferably be 175 mm (7 inches) or
200mm (8 inches) either square or
round and MUST NOT BE LESS
THAN 150 mm (6 INCHES).
Please take care when installing the
stove that the requirements of the
Health and Safety at Work Act 1974
are met.
It is important that there is sufficient
draw in the chimney and that the
chimney does not suffer from down-
draught. When the chimney is warm
the draw should be not less than 2.54
mm (0.10 inches) water gauge. If in
doubt about the chimney seek expert
advice.
Some types of fire cement are caustic
and should not be allowed to come
into contact with the skin. In case of
contact wash with plenty of water.
If an existing chimney is to be used it
must be swept and checked, it must be
in good condition, free from cracks
and blockages, and should not have an
excessive cross sectional area (e.g.
greater than 250mm x 250mm). If you
find that the chimney is in poor
condition then expert advice should be
sought regarding the necessity of
having the chimney lined. If it is
If there is a possibility of disturbing
any asbestos in the course of
installation then please use appropriate
protective equipment.
HEARTH AND FIRE
SURROUND
The stove must stand on a fireproof
hearth and must be situated at least
300mm (12 inches) from any
combustible material. The positioning
of the stove and the size of the hearth
are governed by building regulations
for Class 1 appliances. These building
regulations state that the hearth must
extend in front of the stove by at least
300mm (12 inches) and to the sides of
the stove by at least 150mm (6
inches). If in doubt as to the
There must not be an extractor fan
fitted in the same room as the stove as
this can cause the appliance to emit
fumes into the room.
There must be an adequate air supply
into the room in which the appliance is
installed totalling at least 100 square
cm. (16 square inches) to provide
combustion air. This is particularly
necessary if the room is double glazed.
found necessary to line the chimney
Boiler
Output
(kW)
Do not light the fire before the boiler
has been connected to the system and
filled with water, as this can cause
serious damage to the boiler.
12.0
10.0
8.0
6.0
4.0
2.0
0
positioning of the stove expert advice
should be sought either from the
supplier or the local building
inspector.
In addition to these instructions the
requirements of BS.8303 and BS.6461
Pt 1&2; 1984 must be fulfilled. Local
Authority Bylaws and Building
Regulations regarding the installation
of Solid Fuel burning appliances, flues
and chimneys must also be observed.
The fireplace must allow good
circulation of air around the appliance
to ensure that maximum heat is
transferred to the room and also to
prevent the fireplace from
overheating. A gap of 150mm (6
inches) each side and 300mm (12
inches) above the appliance should
give sufficient air circulation. If a
wooden mantelpiece or beam is used
in the fireplace it should be a
minimum of 460mm (18 inches), and
preferably 600mm (24 inches) from
the appliance. In some situations it
may be necessary to shield the beam
or mantelpiece to protect it.
0
1.0 2.0 3.0 4.0
Space Output
PERFORMANCE
(kW)
The output of the Country 14B is 10.5
kW (35,800 Btu/h) to water and 3.7
kW (12,600 Btu/h) to the room. The
outputs were obtained burning
smokeless fuel over a four hourly re-
fuelling cycle with the doors closed.
Fig. 4. Performance Chart
then a lining suitable for Solid Fuel
must be used.
If there is no existing chimney then a
prefabricated block chimney or a twin
walled insulated stainless steel flue to
BS.4543 can be used either internally
or externally. These chimneys must be
fitted in accordance with the
The heat output to the room is directly
proportional to the heat output to
water as shown in Fig. 4. This means
that if the water heating load is less
than the rated output then the room
heating will be reduced by the same
proportion. This must be borne in
mind when calculating the heating
requirements.
CENTRAL HEATING
SYSTEM
The central heating system must
comply with BS:5449 part 1.
manufacturers instructions and
Building Regulations.
Single wall flue pipe is suitable for
connecting the stove to the chimney
but is not suitable for using for the
If the system is to be a combined
heating and domestic hot water system
then a double feed indirect hot water
storage cylinder to BS:1556 part 1
Page 5
Country 14B 09/03
should be used. In order to prevent the
build up of scale and corrosion a
suitable inhibitor should be used. The
system must be correctly vented as
shown in Figs. 5 and 6. The height
differential between the header tank
and the appliance must not exceed
15.2 metres (50 feet).
22mm Open Vents
Feed and Expansion Tank
Overflow
Cold Water Tank
Overflow
Domestic Hot Water Draw Off
If all four boiler tappings are used
then, if possible, diagonal pairs should
be connected for domestic hot water
and central heating. Where a common
return is used an injector tee must be
incorporated into the system as shown
in Fig. 7. This will ensure that a good
domestic hot water supply is
Gravity Radiator
Drain Cock
Indirect Hot Water Cylinder
maintained when the central heating
pump is operating.
Central Heating Flow
Circulating Pump
Central Heating Return
Minimum Return
Thermostat
The system must incorporate a gravity
circuit which will normally heat the
domestic hot water and an unvalved
radiator with an output of at least 1
kW. When the appliance is not
connected to a domestic hot water
system the unvalved radiator(s) on the
gravity circuit must have an output of
at least 1.25 kW. This is to prevent
boiling in case of pump failure. All
pipework in the primary circuit must
be 28 mm diameter and the gravity
flow pipe must rise continuously from
the boiler to the open vent. Two
typical systems are shown in Figures
5. and 6.
Drain Cock at Lowest Point
Fig. 5. Typical Central Heating & Hot Water System
Using 4 Boiler Tappings
22mm Open Vents
Feed and Expansion Tank
Overflow
Cold Water Tank
Overflow
Domestic Hot Water Draw Off
If the appliance is used to heat a small
central heating system then the heat
output to the room from the fire will
be reduced. Fig. 4. shows the ratio of
space heating to water heating which
can be expected.
Gravity Radiator
Drain Cock
Indirect Hot Water Cylinder
Fitting a radiator in the same room as
the fire is recommended as it will
allow greater flexibility in the way
that the system is operated as well as
ensuring that there is sufficient heat.
Minimum Return Thermostat
Circulating Pump
Central Heating Flow
Connect the heating system to the
boiler ensuring that the primary flow
pipe rises continuously from the
appliance to the vent. Fill the system
with water and check for leaks.
Central Heating Return
Drain Cock at Lowest Point
Injector Tee
Fig. 6. Typical Central Heating & Hot Water System
Using 3 Tappings
SYSTEM CONTROLS
The circulating pump may be
controlled by means of time switches,
room thermostats or outdoor
thermostats. Radiators may be either
manually or thermostatically
Gravity Return
(28mm Pipe)
controlled. These controls will all
work in conjunction with the
thermostat on the appliance and the
low limit pipe thermostat.
Common Return to Boiler
(28mm Pipe)
Central Heating Return
We recommend fitting a pipe
thermostat onto the gravity return to
Fig. 7. Injector Tee.
Page 6
Country 14B 09/03
Back of the Stove
Blanking Plate
Alternative
Soot Door
Positions
Soot Door
In Side or Rear
Of Chimney
Register Plate
With Soot Door
Clamping Plate
with fold horizontal
Blanking Plate
Clamping plate finishes
flush with inside face of
firebox top and bottom.
Fig 8. Vertical Register Plate
With Bricked Up Fireplace
Seal Blanking Plate
with fire cement
Fig 11. Horizontal Register Plate
With Optional Vertical
Alternative
Soot Door
Positions
Rear Flue Connector
Fig. 12. Flue Blanking Plate.
chimney or in the register
plate. Various types and positions of
soot doors are shown in figures 8 to
10.
on the boiler faces and will thereby
increase the life of the boiler. It will
also ensure that priority is given to the
domestic hot water. These thermostats
are available from ourselves if you are
unable to obtain them locally.
Register Plate
With Soot Door
THERMOSTAT
Before lighting the fire check the cold
setting distance of the thermostat.
CONNECTIONS TO
FLUES
There are several ways of connecting
the stove to the flue. These are
illustrated in figures 8 to 10.
Remove the cover plate on the left
hand side of the stove to give access to
the thermostat. With the control knob
at the maximum setting the flap
Fig 9. Horizontal Register Plate
With Rear Flue Connection
should be 18 mm from the air inlet as
shown in Fig. 13. To adjust the
distance slacken the locking nut and
adjust as necessary. When set correctly
If the optional vertical rear flue
connector is used then the chimney
may be swept through the appliance.
Alternative
Soot Door
Positions
Horizontal lengths of flue must be
kept to a minimum and should not be
more than 150mm (6 inches) long.
The sealing face of the flue collar
must be coated with fire cement
before fixing to the body of the stove
using the two screws provided. The
blanking plate must be removed,
sealed with fire cement and refitted,
care being taken to ensure that the fold
on the clamping plate is in line with
the lugs on the firebox as shown in
Fig. 12. Ensure the clamping plate
does not prevent the throat plate from
seating correctly. All flue connections
must be well sealed.
18mm
Register Plate
With Soot Door
Fig 10. Horizontal Register Plate
With Top Flue Connection
SOOT DOORS
Locking Nut
It is possible to pass a 16 inch
Thermostat Flap
act as a low limit thermostat This
should be wired into the mains supply
to the pump so that if the gravity
return temperature drops below 45º C
then the pump will cut out. This will
help to prevent condensation forming
diameter sweeps brush through the
appliance but in most back outlet
installations it will be necessary to
have a soot door to enable the
chimney to be swept. This may either
be in the actual brickwork of the
Fig. 13. Thermostat Setting
Page 7
Country 14B 09/03
re-tighten the locking nut. Ensure that
the flap opens and closes freely as the
knob is turned.
3. The throat plate must be fitted in the
roof of the appliance and should be
checked to ensure that it has not
become dislodged in transit. The
method of location and positioning of
the throat plate is shown in Fig. 3.
The central heating pump should be
adjusted to give the correct water flow
against the circuit resistance and the
system should be correctly balanced.
On completion of the installation and
commissioning please leave the
operating instructions with the
customer and advise on the use of the
appliance and any controls on the
system.
PRE LIGHTING
CHECK
Before initial lighting the following
points should be checked :-
COMMISSIONING
On completion of the installation and
after allowing a suitable period of time
for the fire cement and mortar to dry
out, the stove should be lit and
checked to ensure that smoke and
fumes are taken from the appliance up
the chimney and emitted safely. Also
check all joints and seals.
1. The bottom grate bars must all be
fitted and should move freely and
easily when the riddling mechanism is
operated.
2. The plates round the sides and back
of the grate must be in position and
sitting correctly.
Flue connection may
be Top or Rear
Boiler tappings are 1" BSP Female
136
601
ø154
136
357
340
451
608
789
731
683
570
616
389
136
344
Country 14B Dimensions
(All dimensions are in mm)
Page 8
Country 14B 09/03
Issue C
CHARNWOOD COUNTRY 14B PARTS LIST
35
46
45
9
23
Item 24 has been replaced by items 51 & 52
but they are not interchangeable.
36
42
26
14
7
6
52
13
10
15
11
21
12
31
39
41
40
37
38
43
16
30
32
27
28
15
21
29
17 31 19
20
8
7
6
23 22 33
25
24 34
24 26
51
Item Part No.
Description
Item Part No.
Description
1*
2*
3*
4*
5*
6
7
8
9
008/FV35L
008/FV35R
008/FV35/S
008/FW29
008/TW44S
006/LW30
004/EW23
002/FV07
010/NV31
012/NV14/1
012/FV14/2
012/FV14/3
012/FV14/4
004/FV15
Left Hand Door Seal
Right Hand Door Seal
Door Seal Set Incl. Adhesive
Door Seal Adhesive
Glass Channel (set of 8)
Glass (Inc Channel)
Glazing Bar
36
37
38
39
40
41
42
43
45
46
009/CO14B/A
002/TW34
008/FW48
008/FV49
008/BW50
012/FV10B/19
012/FV11
012/FW34
010/TW33
012/TW09
Firebox / Boiler Assy (Country 14B)
Riddler Knob & Lever
Thermostat
Thermostat Flap
Thermostat Knob
Thermostat Cover
Serial No. Label
Scraper Tool
Vert. Rear Flue Connector (Opt'l Extra)
Blanking Plate
Front Firebars
Throat Plate
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
Secondary Air Slide
Secondary Air Slide Guide
Secondary Air Slide Retainer
Secondary Air Cover
Secondary Air Rod
Side Fire Plate
47* 012/TW14
48* 004/FV18
49* 010/BW51
50* 008/TH02/L
51
52
Primary Air Slide
Primary Air Slide Guide
Ash Carrier (Optional Extra)
Low Level Pipe Stat (Opt'l Extra)
R.H. Door Knob & Spindle
Door Catch Cam
002/EW15
002/BV16
002/DY18
002/KV14
Back Fire Plate
Bottom Grate Bar
002/CG01
002/CG01S14
004/FV17L
004/FV17R
004/BV19
008/BW39/S
008/FW27
008/FV03/A
002/BV12
002/TW13
012/BV20/A
012/BV22/A
002/BV30
Set of Grate Bars (14 per set)
Left Hand Ashpan
Right Hand Ashpan
Ash Shedding Plate
Hinge Pin Set (4 per set)
Hinge Post
Door Catch Assembly
Left Hand Door Knob
Air Control Knob
Ashpan / Door Opening Tool
Riddling Tool
Carrier Bar
Mover Bar
012/BV33
012/BV23
012/CG05
002/FV01
002/FV02
Riddler Rod
Idler Rod
Left Hand Door
Right Hand Door
Flue Collar
002/CH12B
* These items are not shown on the drawing.
To obtain spare parts please contact your local stockist
giving Model, Part No. and Description. In case of
difficulty contact the manufacturer at the address shown.
This drawing is for identification purposes only.
C H A R N W O O D B i s h o p s W a y , N e w p o r t , I s l e o f W i g h t P O 3 0 5 W S , U n i t e d K i n g d o m
T : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 9 9 F : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d @ a j w e l l s . c o . u k w w w . c h a r n w o o d . c o m
Your Local Charnwood Dealer
C H A R N W O O D B i s h o p s W a y , N e w p o r t , I s l e o f W i g h t P O 3 0 5 W S , U n i t e d K i n g d o m
T : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 9 9 F : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d @ a j w e l l s . c o . u k w w w . c h a r n w o o d . c o m
|