Charnwood Electric Heater Country 14B User Manual

CHARNWOOD  
COUNTRY 14B  
Roomheater with Boiler  
Operating  
and  
Installation Instructions  
C H A R N W O O D B i s h o p s W a y , N e w p o r t , I s l e o f W i g h t P O 3 0 5 W S , U n i t e d K i n g d o m  
T : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 9 9 F : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d @ a j w e l l s . c o . u k w w w . c h a r n w o o d . c o m  
 
or fire lighters, and kindling on the  
grate and cover with approximately 2  
inches of fuel. Turn the control knob  
to maximum, and open the airwash  
control fully (see Fig. 1). Light the  
paper or fire lighters. Close the doors  
until the fuel is well ignited then load  
with fuel and adjust the air controls to  
the required setting.  
firebox in two stages waiting between  
each stage for the flames to appear  
above the fire.  
REFUELLING  
Keep the firebox well filled but do not  
overfill to prevent fuel from spilling  
over the top of the front fire bars.  
After a period of slumbering always  
turn the air control up to maximum  
and wait until flames appear above the  
fuel bed before opening the doors.  
Care should be taken especially when  
burning wood that fuel does not  
project over the front fire bars or  
damage to the glass may be caused  
when the doors are closed, it can also  
cause the glass to black up.  
Burning coal will produce more soot  
deposits than other fuels, especially if  
the fire is run at low levels for long  
periods. It is therefore vital to clean  
the throat plate regularly, weekly  
cleaning is recommended.  
On initial lighting, the stove may  
smoke and give off an odour as the  
silicon paint with which the firebox is  
painted reacts to the heat. This is  
normal and will cease after a short  
time, but meanwhile the room should  
be kept well ventilated.  
Never fully close the Airwash control  
when burning coal.  
When relighting the stove, riddle (if  
burning solid fuel), remove any  
clinker from the firebed and then  
empty the ashpan.  
SPECIAL POINTS  
WHEN BURNING  
WOOD AND PEAT  
CONTROLLING THE  
FIRE  
The rate of burning and hence the  
output is controlled by the control  
knob on the side of the fire and the  
airwash control (see Fig.1).  
The grate should be kept in the wood  
burning position and should not be  
riddled until the ash becomes so deep  
that it begins to block the passage of  
air into the firebox at the side of the  
grate. When this is the case do not  
remove all of the ash using the  
Solid Fuel  
Riddle  
riddling mechanism but keep a layer  
about half an inch thick as this enables  
the wood to burn more effectively.  
When burning wood or peat use the  
airwash control in the same way as  
described (see "CONTROLLING  
THE FIRE" )  
The control knob is linked to a  
thermostat which senses the boiler  
temperature. The number at the front  
of the knob is the number at which it  
is set.  
Wood  
The airwash control should be kept at  
least slightly open most of the time to  
keep the glass clean. It may be fully  
opened when rapid heating is required  
or to help clean any deposits from the  
glass. It will not be possible to keep  
the glass clean if this control is fully  
closed, particularly immediately after  
refuelling.  
OVERNIGHT  
BURNING  
For overnight burning the fire doors  
must be closed.  
Fig 2. Grate Operation  
ASH CLEARANCE  
The ashpans should be emptied  
When burning solid fuel the ashpans  
should be emptied and the fire riddled.  
If the fire is very low then it may be  
necessary to add a little fuel and turn  
the thermostat control up to maximum  
for a brief period until the fire is  
burning brightly before filling with  
fuel. When the new fuel has ignited,  
the thermostat control should be  
turned down to the required setting  
and the airwash control moved to a  
low setting. If the central heating  
pump is off overnight then the  
regularly before it becomes too full.  
Never allow the ash to accumulate in  
the ashpans so that it comes in contact  
with the underside of the grate as this  
will seriously damage the grate bars.  
The ashpans are handled using the tool  
provided. Care should be taken to  
ensure that ash is cool before  
RIDDLING  
When burning solid fuels riddling  
twice a day is usually sufficient. When  
burning wood or peat, ash should be  
allowed to build up and generally  
weekly riddling will be sufficient. The  
fire should be riddled with the doors  
shut (see Fig 2.) Place the tool onto  
the riddling lever and rotate between  
the 1 o'clock and 3 o'clock positions  
several times. Too much riddling can  
result in emptying unburnt fuel into  
the ashpan and should therefore be  
avoided. If any clinker forms it should  
be removed from the firebed. After  
riddling, the grate should be put back  
into the solid fuel or wood position as  
required (the tool should be in the 1  
o'clock position for solid fuel or in the  
5 o'clock position for wood).  
emptying it into plastic liners or bins.  
To make ash removal easier there is a  
special Charnwood ash carrier  
available. This may be purchased from  
your supplier or, in case of difficulty,  
from ourselves.  
thermostat may be left at the same  
setting for both day and night  
operation. If the central heating pump  
is on overnight then set the thermostat  
control to give the required level of  
heating. Some experimentation will be  
necessary to find the settings most  
suitable for the particular fuel used  
and the draw on the chimney.  
SPECIAL POINTS  
WHEN BURNING  
COAL  
When loading the stove take care not  
to smother the fire, instead fill the  
To revive the fire, empty the ashpans,  
Page 2  
Country 14B 09/03  
 
riddle, and open the air controls to  
maximum. When the fire is burning  
well load on more fuel as necessary  
and move the air controls to the  
desired setting.  
retaining lugs.  
that a suitable fuel is being used, d)  
that there is an adequate air supply  
into the room,  
e) that an extractor fan is not fitted in  
the same room as the stove.  
f) there is sufficient draw in the  
chimney, (once the chimney is warm a  
draught reading of at least 0.10 inches  
water gauge should be obtained).  
CHIMNEY SWEEPING  
The chimney should be swept at least  
twice a year. Where a top outlet is  
used it will generally be possible to  
sweep the chimney through the  
appliance.  
When burning wood use large logs  
rather than small ones. Proceed as  
above, but do not riddle the fire either  
when shutting down or reviving.  
First remove the side fire plates, front  
firebars and the throat plate. Then  
sweep the chimney ensuring that soot  
is removed from all horizontal  
surfaces after sweeping.  
Door Glass Blacks Up  
CLEANINGAND  
MAINTENANCE  
The stove is finished with a high  
temperature paint which will  
Keeping the glass clean requires a  
certain amount of experimentation due  
to the differences in the draw of  
different chimneys. The following  
points should be noted and with a little  
care should enable the glass to be kept  
clean in most situations:  
In situations where it is not possible to  
sweep through the appliance the  
installer will have provided alternative  
means, such as a soot door. After  
sweeping the chimney the appliance  
flue outlet and the flue pipe  
withstand the temperatures  
encountered in normal use. This may  
be cleaned with a damp lint-free cloth  
when the stove is cold. Should re-  
painting become necessary, high  
temperature paints are available from  
your supplier or from stove shops.  
a) The airwash relies on a supply of  
heated air to keep the glass clean,  
therefore, when lighting the stove  
allow the firebed to become well  
established before closing the air  
controls. This may also be necessary  
when re-fuelling the stove.  
connecting the stove to the chimney  
must be cleaned with a flue brush.  
The glass in the doors is a zero  
expansion ceramic glass, capable of  
withstanding the heat of the fire.  
After clearing any soot from within  
the stove, replace the throat plate (see  
Fig. 3), the front firebars, and side  
fireplates.  
Before cleaning the glass open the  
doors and allow them to cool. Clean  
the glass using a damp cloth and then  
wiping over with a dry cloth. Any  
stubborn deposits on the glass may be  
removed with a proprietary stove glass  
cleaner or ceramic hob cleaner. Some  
deposits on the glass may be burnt off  
simply by running the fire at a fast rate  
for a few minutes. Do not use abrasive  
cleaners or pads as theses can scratch  
the surface which will weaken the  
glass and cause premature failure.  
b) When re-fuelling keep the fuel as  
far back from the front firebars as  
possible, do not try to fit too much  
fuel into the firebox.  
Different types of sweep's brushes are  
available to suit different flueways.  
For standard brick chimneys a wire  
centre sweep's brush fitted with a  
guide wheel is recommended. For  
prefabricated insulated chimneys the  
manufacturers instructions with regard  
to sweeping should be consulted.  
c) Never completely close the airwash  
control - as a guide it should be at  
least a quarter open.  
d) Wet wood or logs overhanging the  
front firebars will cause the glass to  
blacken.  
It is always more difficult to keep the  
glass clean when running the stove  
very slowly for long periods.  
THROAT PLATE AND  
FLUEWAY CLEANING  
It is important that the throat plate and  
all the stove flueways are kept clean.  
When burning smokeless fuels they  
should be cleaned monthly. When  
burning other fuels they should be  
cleaned at least once a week, and more  
frequently if necessary. It is not  
If blackening of the glass still occurs  
check that all flue connections and the  
blanking plate are well sealed. It is  
also important that the chimney draw  
is sufficient, (when the chimney is  
warm a draught reading of at least  
2.54 mm, or 0.10 inches, water gauge  
should be obtained), and that it is not  
affected by down-draught.  
Tool  
Pull Forward  
Swing Down  
necessary to let the fire out completely  
to carry out these operations.  
When burning coal some blackening  
of the glass may occur below the level  
of the front firebars. This will not  
obscure the view of the fire or affect  
its performance.  
The throat plate is lowered using the  
door opening tool. Slide the tool into  
the bracket from the side, pull the  
throat plate forward, and then lower it  
as shown in Fig. 3. Any sooty deposits  
should then be swept from the plate  
and into the fire.  
Fig.3 Throat Plate Location  
Fume Emission.  
TROUBLE SHOOTING  
Fire Will Not Burn.  
Check that:  
a) the air inlet is not obstructed in any  
way,  
Warning Note: Properly installed  
and operated this appliance will not  
emit fumes. Occasional fume from  
de-ashing and re-fuelling may occur.  
Persistent fume emission is  
potentially dangerous and must not  
be tolerated. If fume emission does  
persist, then the following  
While the throat plate is lowered clean  
any sooty deposits from the boiler  
faces and the airwash tubes.  
Return the throat plate to its correct  
position - raise the front of the plate,  
push it back and then lower it onto the  
b) chimneys and flueways are clear, c)  
Page 3  
Country 14B 09/03  
 
immediate actions should be taken:  
f) Door seals and airwash slide are  
intact.  
b) the throat plate is fitted correctly  
(see Fig. 3.) and that it is not distorted.  
c) the door seals are in good condition.  
d) If the hot water goes cold when the  
pump is turned on, or if some radiators  
are hotter than others, then the system  
may need balancing, the pump may be  
pumping the water too quickly around  
the system, or the radiators may need  
bleeding. Please ask your installer to  
check these points.  
a) Open doors and windows to  
ventilate the room.  
b) Let the fire out and safely dispose  
of the fuel from the appliance.  
c) Check for flue or chimney  
blockage, and clean if required.  
d) Do not attempt to re-light the fire  
until cause of fume has been  
identified, if necessary seek  
professional advice.  
Over-Firing  
If the fire is over-fired it will cause  
premature failure of the internal fire  
parts. Overfiring is occurring when  
any parts of the fire begin to glow red.  
To prevent over-firing ensure that:  
a) the door seals are kept in good  
condition, and that the doors are  
sealing correctly,  
b) the thermostat on the fire is  
working correctly,  
c) a suitable fuel is being used,  
d) the fire is not fitted onto a heating  
system which is too large.  
The most common cause of fume  
emission is flueway or chimney  
blockage. For your own safety these  
must be kept clean.  
Chimney Fires.  
If the chimney is thoroughly and  
regularly swept, chimney fires should  
not occur. However, if a chimney fire  
does occur turn the controls to the  
minimum setting, and tightly close the  
doors of the appliance. This should  
cause the chimney fire to go out in  
which case the controls should be kept  
at the minimum setting until the stove  
has gone out. The chimney and  
flueways should then be cleaned. If  
the chimney fire does not go out when  
the above action is taken then the fire  
brigade should be called immediately.  
Fire blazing out of control  
Check that :  
Freezing  
Do not light the fire if there is any  
possibility that any parts of the system  
may be frozen.  
a) The doors are tightly closed.  
b) The aircontrols are set at the  
minimum setting.  
c) the thermostat flap is closed (at the  
bottom of the left hand side of the  
appliance, see Fig. 1.) and that it is not  
prevented from closing completely by  
a piece of ash,  
Lack of Heat To  
Radiators / Hot Water  
After a chimney fire the chimney  
should be carefully examined for any  
damage. Expert advice should be  
sought if necessary.  
d) The airwash control is closed.  
e) A suitable fuel is being used.  
Check that:  
a) the fire is burning properly - if not  
then carry out the checks under "Fire  
Will Not Burn".  
Page 4  
Country 14B 09/03  
 
INSTALLATION INSTRUCTIONS FOR THE  
CHARNWOOD COUNTRY 14B  
complete chimney.  
HEALTH AND SAFETY  
CHIMNEY  
If it is found that there is excessive  
draw in the chimney then a draught  
stabilizer should be fitted.  
PRECAUTIONS  
In order for the appliance to perform  
satisfactorily the chimney height must  
not be less than 4 metres measured  
vertically from the outlet of the stove  
to the top of the chimney. The internal  
dimensions of the chimney should  
preferably be 175 mm (7 inches) or  
200mm (8 inches) either square or  
round and MUST NOT BE LESS  
THAN 150 mm (6 INCHES).  
Please take care when installing the  
stove that the requirements of the  
Health and Safety at Work Act 1974  
are met.  
It is important that there is sufficient  
draw in the chimney and that the  
chimney does not suffer from down-  
draught. When the chimney is warm  
the draw should be not less than 2.54  
mm (0.10 inches) water gauge. If in  
doubt about the chimney seek expert  
advice.  
Some types of fire cement are caustic  
and should not be allowed to come  
into contact with the skin. In case of  
contact wash with plenty of water.  
If an existing chimney is to be used it  
must be swept and checked, it must be  
in good condition, free from cracks  
and blockages, and should not have an  
excessive cross sectional area (e.g.  
greater than 250mm x 250mm). If you  
find that the chimney is in poor  
condition then expert advice should be  
sought regarding the necessity of  
having the chimney lined. If it is  
If there is a possibility of disturbing  
any asbestos in the course of  
installation then please use appropriate  
protective equipment.  
HEARTH AND FIRE  
SURROUND  
The stove must stand on a fireproof  
hearth and must be situated at least  
300mm (12 inches) from any  
combustible material. The positioning  
of the stove and the size of the hearth  
are governed by building regulations  
for Class 1 appliances. These building  
regulations state that the hearth must  
extend in front of the stove by at least  
300mm (12 inches) and to the sides of  
the stove by at least 150mm (6  
inches). If in doubt as to the  
There must not be an extractor fan  
fitted in the same room as the stove as  
this can cause the appliance to emit  
fumes into the room.  
There must be an adequate air supply  
into the room in which the appliance is  
installed totalling at least 100 square  
cm. (16 square inches) to provide  
combustion air. This is particularly  
necessary if the room is double glazed.  
found necessary to line the chimney  
Boiler  
Output  
(kW)  
Do not light the fire before the boiler  
has been connected to the system and  
filled with water, as this can cause  
serious damage to the boiler.  
12.0  
10.0  
8.0  
6.0  
4.0  
2.0  
0
positioning of the stove expert advice  
should be sought either from the  
supplier or the local building  
inspector.  
In addition to these instructions the  
requirements of BS.8303 and BS.6461  
Pt 1&2; 1984 must be fulfilled. Local  
Authority Bylaws and Building  
Regulations regarding the installation  
of Solid Fuel burning appliances, flues  
and chimneys must also be observed.  
The fireplace must allow good  
circulation of air around the appliance  
to ensure that maximum heat is  
transferred to the room and also to  
prevent the fireplace from  
overheating. A gap of 150mm (6  
inches) each side and 300mm (12  
inches) above the appliance should  
give sufficient air circulation. If a  
wooden mantelpiece or beam is used  
in the fireplace it should be a  
minimum of 460mm (18 inches), and  
preferably 600mm (24 inches) from  
the appliance. In some situations it  
may be necessary to shield the beam  
or mantelpiece to protect it.  
0
1.0 2.0 3.0 4.0  
Space Output  
PERFORMANCE  
(kW)  
The output of the Country 14B is 10.5  
kW (35,800 Btu/h) to water and 3.7  
kW (12,600 Btu/h) to the room. The  
outputs were obtained burning  
smokeless fuel over a four hourly re-  
fuelling cycle with the doors closed.  
Fig. 4. Performance Chart  
then a lining suitable for Solid Fuel  
must be used.  
If there is no existing chimney then a  
prefabricated block chimney or a twin  
walled insulated stainless steel flue to  
BS.4543 can be used either internally  
or externally. These chimneys must be  
fitted in accordance with the  
The heat output to the room is directly  
proportional to the heat output to  
water as shown in Fig. 4. This means  
that if the water heating load is less  
than the rated output then the room  
heating will be reduced by the same  
proportion. This must be borne in  
mind when calculating the heating  
requirements.  
CENTRAL HEATING  
SYSTEM  
The central heating system must  
comply with BS:5449 part 1.  
manufacturers instructions and  
Building Regulations.  
Single wall flue pipe is suitable for  
connecting the stove to the chimney  
but is not suitable for using for the  
If the system is to be a combined  
heating and domestic hot water system  
then a double feed indirect hot water  
storage cylinder to BS:1556 part 1  
Page 5  
Country 14B 09/03  
 
should be used. In order to prevent the  
build up of scale and corrosion a  
suitable inhibitor should be used. The  
system must be correctly vented as  
shown in Figs. 5 and 6. The height  
differential between the header tank  
and the appliance must not exceed  
15.2 metres (50 feet).  
22mm Open Vents  
Feed and Expansion Tank  
Overflow  
Cold Water Tank  
Overflow  
Domestic Hot Water Draw Off  
If all four boiler tappings are used  
then, if possible, diagonal pairs should  
be connected for domestic hot water  
and central heating. Where a common  
return is used an injector tee must be  
incorporated into the system as shown  
in Fig. 7. This will ensure that a good  
domestic hot water supply is  
Gravity Radiator  
Drain Cock  
Indirect Hot Water Cylinder  
maintained when the central heating  
pump is operating.  
Central Heating Flow  
Circulating Pump  
Central Heating Return  
Minimum Return  
Thermostat  
The system must incorporate a gravity  
circuit which will normally heat the  
domestic hot water and an unvalved  
radiator with an output of at least 1  
kW. When the appliance is not  
connected to a domestic hot water  
system the unvalved radiator(s) on the  
gravity circuit must have an output of  
at least 1.25 kW. This is to prevent  
boiling in case of pump failure. All  
pipework in the primary circuit must  
be 28 mm diameter and the gravity  
flow pipe must rise continuously from  
the boiler to the open vent. Two  
typical systems are shown in Figures  
5. and 6.  
Drain Cock at Lowest Point  
Fig. 5. Typical Central Heating & Hot Water System  
Using 4 Boiler Tappings  
22mm Open Vents  
Feed and Expansion Tank  
Overflow  
Cold Water Tank  
Overflow  
Domestic Hot Water Draw Off  
If the appliance is used to heat a small  
central heating system then the heat  
output to the room from the fire will  
be reduced. Fig. 4. shows the ratio of  
space heating to water heating which  
can be expected.  
Gravity Radiator  
Drain Cock  
Indirect Hot Water Cylinder  
Fitting a radiator in the same room as  
the fire is recommended as it will  
allow greater flexibility in the way  
that the system is operated as well as  
ensuring that there is sufficient heat.  
Minimum Return Thermostat  
Circulating Pump  
Central Heating Flow  
Connect the heating system to the  
boiler ensuring that the primary flow  
pipe rises continuously from the  
appliance to the vent. Fill the system  
with water and check for leaks.  
Central Heating Return  
Drain Cock at Lowest Point  
Injector Tee  
Fig. 6. Typical Central Heating & Hot Water System  
Using 3 Tappings  
SYSTEM CONTROLS  
The circulating pump may be  
controlled by means of time switches,  
room thermostats or outdoor  
thermostats. Radiators may be either  
manually or thermostatically  
Gravity Return  
(28mm Pipe)  
controlled. These controls will all  
work in conjunction with the  
thermostat on the appliance and the  
low limit pipe thermostat.  
Common Return to Boiler  
(28mm Pipe)  
Central Heating Return  
We recommend fitting a pipe  
thermostat onto the gravity return to  
Fig. 7. Injector Tee.  
Page 6  
Country 14B 09/03  
 
Back of the Stove  
Blanking Plate  
Alternative  
Soot Door  
Positions  
Soot Door  
In Side or Rear  
Of Chimney  
Register Plate  
With Soot Door  
Clamping Plate  
with fold horizontal  
Blanking Plate  
Clamping plate finishes  
flush with inside face of  
firebox top and bottom.  
Fig 8. Vertical Register Plate  
With Bricked Up Fireplace  
Seal Blanking Plate  
with fire cement  
Fig 11. Horizontal Register Plate  
With Optional Vertical  
Alternative  
Soot Door  
Positions  
Rear Flue Connector  
Fig. 12. Flue Blanking Plate.  
chimney or in the register  
plate. Various types and positions of  
soot doors are shown in figures 8 to  
10.  
on the boiler faces and will thereby  
increase the life of the boiler. It will  
also ensure that priority is given to the  
domestic hot water. These thermostats  
are available from ourselves if you are  
unable to obtain them locally.  
Register Plate  
With Soot Door  
THERMOSTAT  
Before lighting the fire check the cold  
setting distance of the thermostat.  
CONNECTIONS TO  
FLUES  
There are several ways of connecting  
the stove to the flue. These are  
illustrated in figures 8 to 10.  
Remove the cover plate on the left  
hand side of the stove to give access to  
the thermostat. With the control knob  
at the maximum setting the flap  
Fig 9. Horizontal Register Plate  
With Rear Flue Connection  
should be 18 mm from the air inlet as  
shown in Fig. 13. To adjust the  
distance slacken the locking nut and  
adjust as necessary. When set correctly  
If the optional vertical rear flue  
connector is used then the chimney  
may be swept through the appliance.  
Alternative  
Soot Door  
Positions  
Horizontal lengths of flue must be  
kept to a minimum and should not be  
more than 150mm (6 inches) long.  
The sealing face of the flue collar  
must be coated with fire cement  
before fixing to the body of the stove  
using the two screws provided. The  
blanking plate must be removed,  
sealed with fire cement and refitted,  
care being taken to ensure that the fold  
on the clamping plate is in line with  
the lugs on the firebox as shown in  
Fig. 12. Ensure the clamping plate  
does not prevent the throat plate from  
seating correctly. All flue connections  
must be well sealed.  
18mm  
Register Plate  
With Soot Door  
Fig 10. Horizontal Register Plate  
With Top Flue Connection  
SOOT DOORS  
Locking Nut  
It is possible to pass a 16 inch  
Thermostat Flap  
act as a low limit thermostat This  
should be wired into the mains supply  
to the pump so that if the gravity  
return temperature drops below 45º C  
then the pump will cut out. This will  
help to prevent condensation forming  
diameter sweeps brush through the  
appliance but in most back outlet  
installations it will be necessary to  
have a soot door to enable the  
chimney to be swept. This may either  
be in the actual brickwork of the  
Fig. 13. Thermostat Setting  
Page 7  
Country 14B 09/03  
 
re-tighten the locking nut. Ensure that  
the flap opens and closes freely as the  
knob is turned.  
3. The throat plate must be fitted in the  
roof of the appliance and should be  
checked to ensure that it has not  
become dislodged in transit. The  
method of location and positioning of  
the throat plate is shown in Fig. 3.  
The central heating pump should be  
adjusted to give the correct water flow  
against the circuit resistance and the  
system should be correctly balanced.  
On completion of the installation and  
commissioning please leave the  
operating instructions with the  
customer and advise on the use of the  
appliance and any controls on the  
system.  
PRE LIGHTING  
CHECK  
Before initial lighting the following  
points should be checked :-  
COMMISSIONING  
On completion of the installation and  
after allowing a suitable period of time  
for the fire cement and mortar to dry  
out, the stove should be lit and  
checked to ensure that smoke and  
fumes are taken from the appliance up  
the chimney and emitted safely. Also  
check all joints and seals.  
1. The bottom grate bars must all be  
fitted and should move freely and  
easily when the riddling mechanism is  
operated.  
2. The plates round the sides and back  
of the grate must be in position and  
sitting correctly.  
Flue connection may  
be Top or Rear  
Boiler tappings are 1" BSP Female  
136  
601  
ø154  
136  
357  
340  
451  
608  
789  
731  
683  
570  
616  
389  
136  
344  
Country 14B Dimensions  
(All dimensions are in mm)  
Page 8  
Country 14B 09/03  
 
Issue C  
CHARNWOOD COUNTRY 14B PARTS LIST  
35  
46  
45  
9
23  
Item 24 has been replaced by items 51 & 52  
but they are not interchangeable.  
36  
42  
26  
14  
7
6
52  
13  
10  
15  
11  
21  
12  
31  
39  
41  
40  
37  
38  
43  
16  
30  
32  
27  
28  
15  
21  
29  
17 31 19  
20  
8
7
6
23 22 33  
25  
24 34  
24 26  
51  
Item Part No.  
Description  
Item Part No.  
Description  
1*  
2*  
3*  
4*  
5*  
6
7
8
9
008/FV35L  
008/FV35R  
008/FV35/S  
008/FW29  
008/TW44S  
006/LW30  
004/EW23  
002/FV07  
010/NV31  
012/NV14/1  
012/FV14/2  
012/FV14/3  
012/FV14/4  
004/FV15  
Left Hand Door Seal  
Right Hand Door Seal  
Door Seal Set Incl. Adhesive  
Door Seal Adhesive  
Glass Channel (set of 8)  
Glass (Inc Channel)  
Glazing Bar  
36  
37  
38  
39  
40  
41  
42  
43  
45  
46  
009/CO14B/A  
002/TW34  
008/FW48  
008/FV49  
008/BW50  
012/FV10B/19  
012/FV11  
012/FW34  
010/TW33  
012/TW09  
Firebox / Boiler Assy (Country 14B)  
Riddler Knob & Lever  
Thermostat  
Thermostat Flap  
Thermostat Knob  
Thermostat Cover  
Serial No. Label  
Scraper Tool  
Vert. Rear Flue Connector (Opt'l Extra)  
Blanking Plate  
Front Firebars  
Throat Plate  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
Secondary Air Slide  
Secondary Air Slide Guide  
Secondary Air Slide Retainer  
Secondary Air Cover  
Secondary Air Rod  
Side Fire Plate  
47* 012/TW14  
48* 004/FV18  
49* 010/BW51  
50* 008/TH02/L  
51  
52  
Primary Air Slide  
Primary Air Slide Guide  
Ash Carrier (Optional Extra)  
Low Level Pipe Stat (Opt'l Extra)  
R.H. Door Knob & Spindle  
Door Catch Cam  
002/EW15  
002/BV16  
002/DY18  
002/KV14  
Back Fire Plate  
Bottom Grate Bar  
002/CG01  
002/CG01S14  
004/FV17L  
004/FV17R  
004/BV19  
008/BW39/S  
008/FW27  
008/FV03/A  
002/BV12  
002/TW13  
012/BV20/A  
012/BV22/A  
002/BV30  
Set of Grate Bars (14 per set)  
Left Hand Ashpan  
Right Hand Ashpan  
Ash Shedding Plate  
Hinge Pin Set (4 per set)  
Hinge Post  
Door Catch Assembly  
Left Hand Door Knob  
Air Control Knob  
Ashpan / Door Opening Tool  
Riddling Tool  
Carrier Bar  
Mover Bar  
012/BV33  
012/BV23  
012/CG05  
002/FV01  
002/FV02  
Riddler Rod  
Idler Rod  
Left Hand Door  
Right Hand Door  
Flue Collar  
002/CH12B  
* These items are not shown on the drawing.  
To obtain spare parts please contact your local stockist  
giving Model, Part No. and Description. In case of  
difficulty contact the manufacturer at the address shown.  
This drawing is for identification purposes only.  
C H A R N W O O D B i s h o p s W a y , N e w p o r t , I s l e o f W i g h t P O 3 0 5 W S , U n i t e d K i n g d o m  
T : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 9 9 F : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d @ a j w e l l s . c o . u k w w w . c h a r n w o o d . c o m  
 
Your Local Charnwood Dealer  
C H A R N W O O D B i s h o p s W a y , N e w p o r t , I s l e o f W i g h t P O 3 0 5 W S , U n i t e d K i n g d o m  
T : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 9 9 F : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d @ a j w e l l s . c o . u k w w w . c h a r n w o o d . c o m  
 

Belkin Network Card F8T017 User Manual
Belkin Switch F1DK102UUK User Manual
Berkel Mixer PM10 User Manual
Bernard Welder SPEC JL 13 User Manual
Braun Hair Dryer BC1400 V2 User Manual
Breville Rice Cooker SLC80 User Manual
Broan Ventilation Hood PM390HS User Manual
Brother Sewing Machine 885 V35 User Manual
Campbell Hausfeld Air Compressor HL5401 Series User Manual
Casio Watch 2171 1 User Manual